Mohd Zin, Abdullah Asuhaimi and Saini, Makmur and Mustafa, M.Wazir and Sultan, Ahmad Rizal (2015) New algorithm for detection and fault classification on parallel transmission line using DWT and BPNN based on Clarke’s transformation. Neurocomputing, 168. pp. 983-993. ISSN 1872-8286

Warning
There is a more recent version of this item available.
[thumbnail of New algorithm for detection and fault classi fi cation on parallel transmission line using DW T and BPNN based on Clarke ’s transformation.pdf] Text
New algorithm for detection and fault classi fi cation on parallel transmission line using DW T and BPNN based on Clarke ’s transformation.pdf - Published Version

Download (3MB)

Abstract

This paper presents a new algorithm for fault detection and classification using discrete wavelet transform (DWT) and back-propagation neural network (BPNN) based on Clarke’s transformation on parallel transmission. Alpha and beta (mode) currents generated by Clarke’s transformation were used to convert the signal of discrete wavelet transform (DWT) to get the wavelet transform coefficients (WTC)
and the wavelet energy coefficient (WEC). Daubechies4 (Db4) was used as a mother wavelet to decompose the high frequency components of the signal error. The simulation was performed using PSCAD/EMTDC for transmission system modeling. Simulation was performed at different locations along
the transmission line with different types of fault and fault resistance, fault location and fault initial
angle on a given power system model. Four statistic methods utilized are in the present study to determine the accuracy of detection and classification faults. The results show that the best Clarke transformation occurred on the configuration of 12-24-48-4, respectively. For instance, the errors using mean square error method, the errors of BPNN, Pattern Recognition Network and Fit Network are
0.03721, 0.13115 and 0.03728, respectively. This indicates that the BPNN results are the lowest error

Item Type: Article
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Jurusan Teknik Elektro > D4 Teknik Listrik
Depositing User: Mr Ahmad Rizal Sultan
Date Deposited: 30 Apr 2023 03:53
Last Modified: 30 Apr 2023 03:53
URI: https://repository.poliupg.ac.id/id/eprint/1003

Available Versions of this Item

Actions (login required)

View Item
View Item