Search for collections on PNUP Repository

Identification of Ground–fault Current in Various Transformer Connection and Generator Grounding using Symmetrical Components Method

Sultan, Ahmad Rizal and Mustafa, M.Wazir and Saini, Makmur and Gaffar, Ahmad (2019) Identification of Ground–fault Current in Various Transformer Connection and Generator Grounding using Symmetrical Components Method. In: The 5th Intenational Sympoosium on Material, Mechatronic and Energy, 6-8 November 2019, Makassar, Indonesia.

This is the latest version of this item.

[thumbnail of Sultan_2019_IOP_Conf._Ser. _Mater._Sci._Eng._619_012032.pdf] Text
Sultan_2019_IOP_Conf._Ser. _Mater._Sci._Eng._619_012032.pdf - Published Version

Download (655kB)
[thumbnail of meta] Text
meta - Published Version

Download (120kB)
[thumbnail of ISMME_Serifikat.pdf] Text
ISMME_Serifikat.pdf - Supplemental Material

Download (2MB)
[thumbnail of Proses Review ISMME_2018.pdf] Text
Proses Review ISMME_2018.pdf - Supplemental Material

Download (612kB)

Abstract

Single line to ground-fault (SLG) fault is the record frequent fault probable to occur in an electric power system. The effect of ground-fault is determined by using grounding method and transformer connections. In this study, the simulation showed the performance of a simple
power system within the SLG fault in the system at various transformer connection and generator grounding method. New approach the application of ground fault current calculation using symmetrical components method on unit generator transformers. A symmetrical components method applied with simulation was conducted in Matlab software. The results were then analyzed, presenting a comparison with the fault impact at various transformer connection and generator grounding method. The models of transformer connection for each side (primary and secondary) used were wye (Y), wye-grounded (Yn) and delta (). It was clearly shown that the
ground-fault currents at the generator bus had significantly an effect on the type of the transformer connections used during the ground-fault at the secondary side of the transformer.

Item Type: Conference or Workshop Item (Paper)
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering