Sultan, Ahmad Rizal and Mustafa, M.Wazir (2013) Ground Fault Currents in Unit Generator Transformer at Various Voltage and Transformer Configurations. Indian Journal of Applied Research, 3 (5). pp. 224-227. ISSN 2249-555X
IJAR_2013.pdf - Published Version
Download (182kB)
Abstract
Single line to ground fault (SLGF) is the most frequent fault probable to occur in an electric power system.
The effect of ground fault is determined by voltage transformer and transformer configurations. In this paper,
the simulation showed the performance generator within the SLGF at various transformer configurations. Simulation was
conducted in DIgSILENT PowerFactory 14.0. and the results were analyzed, presenting comparison of the fault impact at
various transformer connections. The model of transformer connection for each side (primary and secondary) used were Y, Yn, Z, Zn and ∆ . The Y, Z and ∆ secondary side of transformer configuration were utilized to block the single line to ground fault at the generator bus. It was clearly shown that the SLGF at the generator bus was highly dependent upon the type of the transformer configurations used during the ground fault at the secondary side of transformer
Item Type: | Article |
---|---|
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Jurusan Teknik Elektro > D4 Teknik Listrik |
Depositing User: | Mr Ahmad Rizal Sultan |
Date Deposited: | 30 Apr 2023 00:21 |
Last Modified: | 14 May 2023 23:24 |
URI: | https://repository.poliupg.ac.id/id/eprint/1024 |
Available Versions of this Item
- Ground Fault Currents in Unit Generator Transformer at Various Voltage and Transformer Configurations. (deposited 30 Apr 2023 00:21) [Currently Displayed]