Pengembangan Sistem Penangkal Petir dan Pentanahan Elektroda Rod dan Plat

Makmur, Saini and A. M, Shiddiq Yunus and Andareas, Pangkung (2016) Pengembangan Sistem Penangkal Petir dan Pentanahan Elektroda Rod dan Plat. Pengembangan Sistem Penangkal Petir dan Pentanahan Elektroda Rod dan Plat, 3 (2). pp. 66-71. ISSN 2339-0700

[img]
Preview
Text (Paper)
10. Pengembangan Sistem Penangkal Petir dan Pentanahan Elektroda Rod dan Plat.pdf - Published Version
Available under License Creative Commons Attribution.

Download (191kB) | Preview
[img]
Preview
Text (Plagiarism)
Plagiarism - Report _Penangkal Petir.pdf

Download (449kB) | Preview
[img]
Preview
Text (Peer Review)
Peer Reviwer Pengembangan Sistim penangkal petir.pdf - Published Version
Available under License Creative Commons Attribution.

Download (225kB) | Preview
Official URL: http://jurnal.poliupg.ac.id/index.php/Intek/articl...

Abstract

The specific objective of this research is to produce a system of internallightning and Eksternal lightning rod with grounding which has been widely used in industries such as lightning protection and grounding system of substation, transmission lines and coupling wire used in high-rise buildings either belong to government or private property. In this study, lightning rod is located outside the building structure that serves to catch or receive the bolt of lightning and the lightning deliver to the ground safely. In this study there were 5 different depths of electrode rod; 3 m, 5 m, 7 m, 9 m, and 12 m, moreover, 5 wide variety of electrode plate that are 1 x 1 m 2 2 , 0.75 x 0.75 m , 0.5 x0. 5 m 2 1 2 , 0.35 x 0.35 m Makmur Saini 2 , 0.25 x 0.25 m . For grounding electrode rod with a depth of 3 m, 5 m, 7 m, 9 m, 12 m in dry conditions grounding resistance values obtained ranged from 1.55 to 2.03 Ohm. For moist soil conditions, grounding resistance values obtained ranged from 2.21 to 2.60 Ohm. For wet soil conditions grounding resistance values obtained ranged from 1.97 to 2.34 Ohm. For grounding plate, R 11 and R on the dry conditions grounding resistance values obtained ranged from 2.08 to 2.45 Ohm. For moist soil conditions grounding resistance values obtained ranged from 1.88 to 2.18 Ohm. For wet soil conditions grounding resistance values obtained ranged from 1.55 to 2.06 Ohm. On the external lightning rod with two added electrodes with a depth of 12 m and then connected in parallel with the electrode plate to get the smallest value of grounding resistance in accordance with the standards prescribed

Item Type: Article
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Department of Mechanical Engineering > Teknik Pembangkit Energi
Depositing User: Ir Makmur Saini, M.T, P.hD
Date Deposited: 13 Dec 2017 23:24
Last Modified: 15 May 2019 00:32
URI: http://repository.poliupg.ac.id/id/eprint/541

Actions (login required)

View Item View Item